ISO 14644 Cleanroom Certification Quotes

ISO 14644 cleanroom certification shows a room meets its ISO class. A certifier counts airborne particles at set locations under ISO 14644-1 and usually adds performance tests from ISO 14644-3, such as HEPA filter leak, airflow and pressure difference. Send one request on Certification Quotes to get multiple certification quotes instead of calling each provider.

Facilities anywhere in the U.S. can request quotes here.

What ISO 14644 cleanroom certification is

ISO 14644-1:2015 classifies air cleanliness by the concentration of airborne particles. It has nine classes, ISO Class 1 (cleanest) to ISO Class 9, and uses particle sizes from 0.1 µm to 5 µm, measured with light-scattering airborne particle counters.

Common limits for particles 0.5 µm and larger, per cubic meter of air:

ISO classMax particles ≥0.5 µm per m³
ISO 53,520
ISO 635,200
ISO 7352,000
ISO 83,520,000

A class is always stated for an occupancy state: as-built, at-rest or operational. The minimum number of sampling locations comes from the room's area (ISO 14644-1, Table A.1).

Certification usually pairs that classification with performance tests from ISO 14644-3, such as airflow, pressure difference, installed filter leakage, airflow direction and recovery. ISO 14644-2 covers ongoing monitoring: a monitoring plan based on risk assessment, with periodic classification done annually unless risk assessment and monitoring data support a longer interval.

Learn more: ISO 14644 explained · ISO 5 · ISO 6 · ISO 7 · ISO 8

Who needs it

  • Any facility that has to show a room or clean zone meets a specified ISO class, whether for a customer, a regulator or its own quality system.
  • New or changed cleanrooms that need an as-built or at-rest classification before use.
  • Operating cleanrooms due for periodic classification under their ISO 14644-2 monitoring plan.
  • Sterile compounding pharmacies, whose rooms are certified to ISO classes under USP <797>. See USP 797 certification.

What to include in your quote request

  • Facility address (city and state is enough to start)
  • Number of rooms and the ISO class of each (for example, 2 rooms at ISO 7 and 1 at ISO 8)
  • Approximate square footage of each room
  • Occupancy state you need tested: as-built, at-rest or operational
  • Tests you want besides particle counts: HEPA filter leak, airflow/air changes, pressure difference, airflow visualization, recovery
  • Number of HEPA filters, and any hoods or cabinets to certify on the same visit
  • Your standard or requirement (ISO 14644-1, USP <797>, a customer spec) and the report format you need
  • Last certification date and when you need the work done

Need quotes? Request quotes with one form →

Are you a certification or testing company? Join as a provider →

How getting quotes works here

  1. Send one request. Use the quote request form to describe your facility, where it is, the rooms or equipment, and the tests or standard you need.
  2. We share it with providers. Your request goes to certification and testing companies that cover your area and the type of work.
  3. Compare and choose. Providers that want the job send quotes. You compare scope and price side by side and pick who to hire, so you don't have to chase each company yourself.

Related services

Requests are accepted nationwide. Browse locations.

FAQ

What does ISO 14644-1 measure?

It measures airborne particle concentration at particle sizes from 0.1 µm to 5 µm, using light-scattering particle counters. It doesn't measure whether particles are viable (living); that needs separate microbial sampling.

How often does an ISO cleanroom need to be reclassified?

ISO 14644-2:2015 calls for periodic classification annually. The interval can be extended if a risk assessment, the monitoring system and consistently compliant data support it. Other rules, such as USP <797>'s 6-month recertification, can require more often.

How many particles can an ISO 7 cleanroom have?

ISO 7 allows up to 352,000 particles 0.5 µm and larger per cubic meter of air. ISO 8 allows 3,520,000 and ISO 5 allows 3,520.

What is the difference between at-rest and operational?

At-rest means the room and equipment are installed and running with no people present. Operational means the room is working normally with people and processes. A class is only meaningful when the state is stated.

Can I bundle HEPA filter testing and hood certification in the same request?

Yes. List everything in one request so providers can quote the full scope for one visit.

Need quotes? Request quotes with one form →

Are you a certification or testing company? Join as a provider →