Cleanroom Recovery Testing Quotes
A cleanroom recovery test shows whether a room returns to a specified cleanliness level within a set time after a brief particle challenge. ISO 14644-3 describes the method, usually as the 100:1 recovery time. It is meant for non-unidirectional airflow rooms. EU GMP Annex 1 uses it in place of velocity tests there.
Facilities anywhere in the U.S. can request quotes here.
What a recovery test is
Under ISO 14644-3, the recovery test determines whether a cleanroom or clean zone can return to a specified cleanliness level within a finite time after brief exposure to an airborne particle challenge.
- Not recommended for unidirectional airflow (hoods, ISO 5 zones)
- Common result: the 100:1 recovery time, which is how long particle concentration takes to fall to 1% of the starting challenge concentration. A recovery rate method is used when a high enough challenge can't be reached.
- Residue: when an artificial aerosol is used, consider the risk of residue contamination
EU GMP Annex 1: for grades with non-unidirectional airflow, a recovery test should replace the air velocity test at requalification.
Who needs it
- Annex 1 facilities with grade B, C or D non-unidirectional rooms
- ISO 14644 cleanrooms where your spec or customer requires recovery
- Rooms after HVAC or layout changes that could affect air distribution
What to include in your quote request
- Facility address
- Rooms to test, with ISO class or grade, area and air supply type
- Recovery method or acceptance time from your spec, if any
- Challenge aerosol restrictions (residue concerns)
- Standard (ISO 14644-3, Annex 1, customer spec)
- Other tests for the same visit
Need quotes? Request quotes with one form →
Are you a certification or testing company? Join as a provider →
How getting quotes works here
- Send one request. Use the quote request form to describe your facility, where it is, the rooms or equipment, and the tests or standard you need.
- We share it with providers. Your request goes to certification and testing companies that cover your area and the type of work.
- Compare and choose. Providers that want the job send quotes. You compare scope and price side by side and pick who to hire, so you don't have to chase each company yourself.
Related
Requests are accepted nationwide. Browse locations.
FAQ
What is a cleanroom recovery test?
It measures how quickly a room returns to its specified cleanliness after a short particle challenge, as described in ISO 14644-3.
What is the 100:1 recovery time?
The time for particle concentration to fall to 1% of the initial challenge concentration after the challenge stops.
Is recovery testing done in laminar flow hoods?
No. ISO 14644-3 doesn't recommend the recovery test for unidirectional airflow.
Does EU GMP Annex 1 require recovery testing?
For grades with non-unidirectional airflow, Annex 1 says a recovery test should replace the air velocity test at requalification.