USP 800 requirements explained
USP General Chapter <800> sets standards for handling hazardous drugs (HDs) in healthcare settings. Sterile and nonsterile HDs must be compounded in a containment hood (C-PEC) inside a room (C-SEC) that is externally vented and held at 0.01 to 0.03 inches of water column negative pressure. Sterile hazardous-drug compounding must also meet USP <797>. Need it done? Get quotes for USP 800 certification.
Facilities anywhere in the U.S. can request quotes here.
What USP <800> certification checks
USP General Chapter <800> sets standards for handling hazardous drugs (HDs) in healthcare settings. Sterile and nonsterile HDs must be compounded in a containment primary engineering control (C-PEC) placed in a containment secondary engineering control (C-SEC).
The C-SEC must:
- Be externally vented
- Be physically separated (a different room from other preparation areas)
- Have an appropriate air exchange rate (ACPH)
- Hold a negative pressure between 0.01 and 0.03 inches of water column relative to all adjacent areas, at all times
Room types and air changes:
- Sterile HD buffer room and ante-room (cleanroom suite): at least 30 ACPH
- Containment segregated compounding area (C-SCA): an unclassified, externally vented room with fixed walls and at least 12 ACPH
- Nonsterile HD compounding room: at least 12 ACPH
For sterile HD compounding, USP <800> also requires the standards in USP <797>, including its certification and 6-month recertification of hoods and rooms. So a sterile HD room is certified under USP 797, with USP 800's negative pressure, venting and air change requirements on top.
Related pages
Requests are accepted nationwide. Browse locations.
FAQ
What pressure does a USP 800 room need?
The C-SEC must be negative between 0.01 and 0.03 inches of water column relative to all adjacent areas, at all times.
How many air changes does a USP 800 room need?
At least 30 ACPH for sterile HD buffer rooms and ante-rooms, and at least 12 ACPH for a C-SCA or a nonsterile HD compounding room.
Does USP 800 replace USP 797?
No. Sterile hazardous-drug compounding must meet both. USP <800> adds containment requirements on top of USP <797>.
Can the negative pressure be turned off when the room isn't in use?
No. USP says the C-SEC must hold its negative pressure and required air changes at all times.