ISO 14644 explained: classes, monitoring and tests
ISO 14644-1:2015 classifies air cleanliness by the concentration of airborne particles. It has nine classes, ISO Class 1 (cleanest) to ISO Class 9. Certification usually pairs that classification with performance tests from ISO 14644-3, such as HEPA filter leak, airflow and pressure difference. ISO 14644-2 covers ongoing monitoring, with periodic classification done annually. Need it done? Get quotes for ISO 14644 certification.
Facilities anywhere in the U.S. can request quotes here.
What ISO 14644 covers
ISO 14644-1:2015 classifies air cleanliness by the concentration of airborne particles. It has nine classes, ISO Class 1 (cleanest) to ISO Class 9, and uses particle sizes from 0.1 µm to 5 µm, measured with light-scattering airborne particle counters.
Common limits for particles 0.5 µm and larger, per cubic meter of air:
| ISO class | Max particles ≥0.5 µm per m³ |
|---|---|
| ISO 5 | 3,520 |
| ISO 6 | 35,200 |
| ISO 7 | 352,000 |
| ISO 8 | 3,520,000 |
A class is always stated for an occupancy state: as-built, at-rest or operational. The minimum number of sampling locations comes from the room's area (ISO 14644-1, Table A.1).
Certification usually pairs that classification with performance tests from ISO 14644-3, such as airflow, pressure difference, installed filter leakage, airflow direction and recovery. ISO 14644-2 covers ongoing monitoring: a monitoring plan based on risk assessment, with periodic classification done annually unless risk assessment and monitoring data support a longer interval.
Related pages
Requests are accepted nationwide. Browse locations.
FAQ
What does ISO 14644-1 measure?
It measures airborne particle concentration at particle sizes from 0.1 µm to 5 µm, using light-scattering particle counters. It doesn't measure whether particles are viable (living); that needs separate microbial sampling.
How often does an ISO cleanroom need to be reclassified?
ISO 14644-2:2015 calls for periodic classification annually. The interval can be extended if a risk assessment, the monitoring system and consistently compliant data support it. Other rules, such as USP <797>'s 6-month recertification, can require more often.
How many particles can an ISO 7 cleanroom have?
ISO 7 allows up to 352,000 particles 0.5 µm and larger per cubic meter of air. ISO 8 allows 3,520,000 and ISO 5 allows 3,520.
What is the difference between at-rest and operational?
At-rest means the room and equipment are installed and running with no people present. Operational means the room is working normally with people and processes. A class is only meaningful when the state is stated.