USP <800> covers handling hazardous drugs. Compounding must happen in a containment hood (C-PEC) inside a room (C-SEC) that is externally vented and held at 0.01 to 0.03 inches of water column negative pressure. Sterile hazardous-drug compounding must also meet USP <797>. Request one set of quotes to compare certifiers.
Facilities anywhere in the U.S. can request quotes here.
What USP <800> certification checks
USP General Chapter <800> sets standards for handling hazardous drugs (HDs) in healthcare settings. Sterile and nonsterile HDs must be compounded in a containment primary engineering control (C-PEC) placed in a containment secondary engineering control (C-SEC).
The C-SEC must:
- Be externally vented
- Be physically separated (a different room from other preparation areas)
- Have an appropriate air exchange rate (ACPH)
- Hold a negative pressure between 0.01 and 0.03 inches of water column relative to all adjacent areas, at all times
Room types and air changes:
- Sterile HD buffer room and ante-room (cleanroom suite): at least 30 ACPH
- Containment segregated compounding area (C-SCA): an unclassified, externally vented room with fixed walls and at least 12 ACPH
- Nonsterile HD compounding room: at least 12 ACPH
For sterile HD compounding, USP <800> also requires the standards in USP <797>, including its certification and 6-month recertification of hoods and rooms. So a sterile HD room is certified under USP 797, with USP 800's negative pressure, venting and air change requirements on top.
Learn more: USP 800 explained
Who needs it
- Pharmacies and healthcare facilities that compound hazardous drugs, sterile or nonsterile
- Sites with BSCs or compounding aseptic containment isolators (CACIs) used as C-PECs
- Facilities adding or changing a negative-pressure HD room or C-SCA
What to include in your quote request
- Facility address and type
- Each HD room: buffer room, ante-room, C-SCA or nonsterile room, with ISO class where classified
- Number of C-PECs by type (BSC class/type, CACI, containment ventilated enclosure), with make and model if known
- Whether the same visit should cover non-HD USP <797> rooms and hoods
- Last certification date and due date
- Any state board or accreditor reporting requirements
Need quotes? Request quotes with one form →
Are you a certification or testing company? Join as a provider →
How getting quotes works here
- Send one request. Use the quote request form to describe your facility, where it is, the rooms or equipment, and the tests or standard you need.
- We share it with providers. Your request goes to certification and testing companies that cover your area and the type of work.
- Compare and choose. Providers that want the job send quotes. You compare scope and price side by side and pick who to hire, so you don't have to chase each company yourself.
Related services
- USP 797 certification
- Biosafety cabinet certification
- HEPA filter testing
- Pressure differential testing
- Particle count testing
Requests are accepted nationwide. Browse locations.
FAQ
What pressure does a USP 800 room need?
The C-SEC must be negative between 0.01 and 0.03 inches of water column relative to all adjacent areas, at all times.
How many air changes does a USP 800 room need?
At least 30 ACPH for sterile HD buffer rooms and ante-rooms, and at least 12 ACPH for a C-SCA or a nonsterile HD compounding room.
Does USP 800 replace USP 797?
No. Sterile hazardous-drug compounding must meet both. USP <800> adds containment requirements on top of USP <797>.
Can the negative pressure be turned off when the room isn't in use?
No. USP says the C-SEC must hold its negative pressure and required air changes at all times.
Can I get USP 797 and USP 800 rooms quoted together?
Yes. List every room and hood in one request.