EU GMP Annex 1 Cleanroom Qualification Quotes (Grades A–D)
EU GMP Annex 1 grades sterile manufacturing cleanrooms A to D. Classification is done at rest and in operation, for example Grade B allows 3,520 particles ≥0.5 µm per m³ at rest and 352,000 in operation. Requalification is required at least every 6 months for grades A and B and every 12 months for C and D. Request quotes here.
Facilities anywhere in the U.S. can request quotes here.
What Annex 1 qualification is
EU GMP Annex 1, Manufacture of Sterile Medicinal Products (revised 2022, in operation since August 25, 2023), defines four cleanroom grades:
- Grade A: the critical zone for high-risk operations, such as the aseptic filling zone
- Grade B: the background cleanroom for Grade A in aseptic preparation and filling
- Grades C and D: cleanrooms for less critical stages
Maximum total particles for classification (Annex 1, Table 1):
| Grade | ≥0.5 µm at rest | ≥0.5 µm in operation | ≥5 µm at rest | ≥5 µm in operation |
|---|---|---|---|---|
| A | 3,520 | 3,520 | Not specified | Not specified |
| B | 3,520 | 352,000 | Not specified | 2,930 |
| C | 352,000 | 3,520,000 | 2,930 | 29,300 |
| D | 3,520,000 | Not predetermined | 29,300 | Not predetermined |
Sampling locations follow ISO 14644-1, with extra locations considered for Grade A and B areas.
Requalification must include at least: cleanroom classification (total particles), final filter integrity test, airflow volume, room pressure differences, and air velocity (risk-based for B, C and D; recovery testing replaces velocity in non-unidirectional rooms). Maximum interval: 6 months for grades A and B, 12 months for grades C and D, and also after remedial action or changes.
Who needs it
- Sterile product manufacturers following EU GMP Annex 1
- Facilities with grade A, B, C or D areas, RABS or isolators
What to include in your quote request
- Facility address
- Each room or zone with its grade and area
- States to test (at rest, in operation)
- Number of final filters, RABS and isolators
- Whether viable monitoring or recovery testing is needed
- Your contamination control strategy (CCS) or protocol requirements, and due date
Need quotes? Request quotes with one form →
Are you a certification or testing company? Join as a provider →
How getting quotes works here
- Send one request. Use the quote request form to describe your facility, where it is, the rooms or equipment, and the tests or standard you need.
- We share it with providers. Your request goes to certification and testing companies that cover your area and the type of work.
- Compare and choose. Providers that want the job send quotes. You compare scope and price side by side and pick who to hire, so you don't have to chase each company yourself.
Related
- ISO 14644 certification
- ISO 5
- HEPA filter testing
- Recovery testing
- Environmental monitoring
- Pressure differential testing
Requests are accepted nationwide. Browse locations.
FAQ
What are the EU GMP cleanroom grades?
Annex 1 uses Grades A, B, C and D. Grade A is the critical zone for high-risk aseptic operations, Grade B is its background, and C and D are for less critical stages.
How often must Annex 1 cleanrooms be requalified?
At most every 6 months for grades A and B and every 12 months for grades C and D, and after remedial action or relevant changes.
What particle limits apply to Grade A?
3,520 particles ≥0.5 µm per m³ both at rest and in operation. A 5 µm limit is not specified but may be considered where the CCS or trends indicate.
Is Grade A the same as ISO 5?
They share the same 3,520 particles per m³ limit at ≥0.5 µm, but Annex 1 adds its own states, monitoring and microbial requirements. Treat them as separate requirements.
When did the revised Annex 1 take effect?
It came into operation on August 25, 2023 (with a later date for one lyophilizer-related point).