Cleanroom Airflow and Air Change Rate Testing
Airflow testing measures how much HEPA-filtered air a cleanroom receives. Velocity readings at filters or in unidirectional zones give speed and uniformity, and airflow volume gives the air change rate (air changes per hour). ISO 14644-3 describes the method, and USP <797> sets minimums such as 30 ACPH for ISO 7 rooms. Request quotes here.
Facilities anywhere in the U.S. can request quotes here.
What airflow testing is
ISO 14644-3 describes the airflow test:
- Unidirectional airflow (hoods, ISO 5 zones): individual velocity readings to measure velocity and uniformity. The average velocity can be used to calculate airflow volume and air change rate.
- Non-unidirectional rooms: airflow volume measured directly, for example at each supply filter, then used to calculate air changes per hour.
The air pressure difference test should follow once airflow meets its acceptance criteria.
USP <797> minimums for sterile compounding rooms:
| Room | Minimum total HEPA-filtered ACPH |
|---|---|
| ISO Class 7 | 30 |
| ISO Class 8 | 20 |
The ACPH from the HVAC, the ACPH contributed by the PEC, and the total must be documented on the certification report. USP <800> requires at least 30 ACPH for sterile HD buffer and ante-rooms and at least 12 ACPH for a C-SCA.
Who needs it
- Cleanrooms being certified to ISO 14644 or requalified under EU GMP Annex 1 (airflow volume is a minimum requalification test)
- USP <797>/<800> pharmacies at each 6-month recertification
- Rooms after HVAC changes, filter replacement or rebalancing
What to include in your quote request
- Facility address
- Rooms with ISO class, area and ceiling height
- Number and type of supply filters (terminal HEPA, fan filter units)
- Unidirectional zones or hoods needing velocity readings
- Standard (ISO 14644-3, USP <797>/<800>, Annex 1)
- Whether you need balancing if a room is low (HVAC TAB)
Need quotes? Request quotes with one form →
Are you a certification or testing company? Join as a provider →
How getting quotes works here
- Send one request. Use the quote request form to describe your facility, where it is, the rooms or equipment, and the tests or standard you need.
- We share it with providers. Your request goes to certification and testing companies that cover your area and the type of work.
- Compare and choose. Providers that want the job send quotes. You compare scope and price side by side and pick who to hire, so you don't have to chase each company yourself.
Related
Requests are accepted nationwide. Browse locations.
FAQ
How is a cleanroom air change rate measured?
Measure the supply airflow volume (directly at the filters, or from average velocity times filter area for unidirectional flow), then divide the hourly airflow by the room volume to get air changes per hour.
How many air changes does a USP 797 cleanroom need?
At least 30 HEPA-filtered ACPH for ISO Class 7 rooms and 20 for ISO Class 8 rooms.
Does ISO 14644 require a minimum air change rate?
No. ISO 14644-3 gives the test method. The required rate comes from your design, USP <797>/<800>, or another regulation.
Can the hood count toward the room's air changes?
Under USP <797>, HEPA-filtered air from the PEC can count toward the ISO 7 total, and the ACPH from the HVAC, the ACPH contributed by the PEC, and the total must be documented on the certification report.
When should airflow be tested relative to pressure?
ISO 14644-3 says the pressure difference test should be done after airflow meets its acceptance criteria.
Need quotes? Request quotes with one form →
Are you a certification or testing company? Join as a provider →