Cleanroom Pressure Differential Testing Quotes

Pressure differential testing confirms that air flows from cleaner rooms to less clean rooms. USP <797> requires at least 0.020 in. water column positive pressure between classified rooms. USP <800> hazardous drug rooms must be 0.01 to 0.03 in. negative. EU GMP Annex 1 gives 10 Pa as a guidance minimum between grades. Request testing quotes here.

Facilities anywhere in the U.S. can request quotes here.

What pressure differential testing is

ISO 14644-3's air pressure difference test verifies that the air system can hold the specified pressure differential between a cleanroom and its surroundings. It should be done after airflow passes its acceptance criteria.

Requirements by standard:

StandardRequirement
USP <797>At least 0.020 in. w.c. positive between each ISO-classified area (e.g., buffer to ante-room), and ante-room to unclassified area at least 0.020 in. w.c. Continuous monitoring with a pressure differential monitoring device.
USP <800>C-SEC negative 0.01–0.03 in. w.c. to all adjacent areas, at all times
USP <825>Positive rooms at least 0.02 in. w.c. between classified areas. Negative pressure for volatile or airborne radiopharmaceuticals per the RAM license.
EU GMP Annex 1Adjacent rooms of different grades: a minimum of 10 Pa (guidance value). Pressure differences are a minimum requalification test.

Who needs it

  • USP <797>, <800> and <825> pharmacies at each recertification
  • ISO 14644 cleanrooms with a specified pressure cascade
  • Annex 1 facilities at requalification
  • Anyone whose pressure monitor alarms or reads out of range

What to include in your quote request

  • Facility address
  • Room list with ISO class or grade and the intended pressure relationship (positive or negative to which room)
  • Whether you have continuous monitors and want them verified against a calibrated reference
  • Standard (USP <797>/<800>/<825>, ISO 14644-3, Annex 1)
  • Whether rebalancing should be quoted if rooms fail (HVAC TAB)

Need quotes? Request quotes with one form →

Are you a certification or testing company? Join as a provider →

How getting quotes works here

  1. Send one request. Use the quote request form to describe your facility, where it is, the rooms or equipment, and the tests or standard you need.
  2. We share it with providers. Your request goes to certification and testing companies that cover your area and the type of work.
  3. Compare and choose. Providers that want the job send quotes. You compare scope and price side by side and pick who to hire, so you don't have to chase each company yourself.

Related

Requests are accepted nationwide. Browse locations.

FAQ

What pressure differential does USP 797 require?

At least 0.020 inches of water column positive between each ISO-classified area, and between the ante-room and the unclassified area.

What pressure does a USP 800 negative room need?

Between 0.01 and 0.03 inches of water column negative to all adjacent areas, at all times.

What is the Annex 1 pressure difference between grades?

Annex 1 gives a minimum of 10 Pascals between adjacent rooms of different grades as a guidance value.

Does USP 797 require continuous pressure monitoring?

Yes. Where pressure differentials are required, a pressure differential monitoring device must continuously monitor them, and results must be reviewed and documented.

Why test airflow before pressure?

ISO 14644-3 says the pressure difference test should follow successful airflow testing, because pressure depends on supply and exhaust air balance.