DOP vs PAO testing for HEPA filters
DOP and PAO are aerosols used to leak-test installed HEPA filters. DOP, also called DEHP, was the older agent; a 1995 U.S. Department of Energy report noted it caused liver tumors in laboratory animals and reviewed substitutes. PAO is now the typical challenge agent. The test is the same idea: aerosol upstream, then a scan downstream for leaks.
Facilities anywhere in the U.S. can request quotes here.
Why one request beats ten forms
On a typical provider's website you fill out a quote form, then repeat that process on the next company's site, and the next. On Certification Quotes you describe the job once—your rooms, hoods, tests and timing—and that request is shared with providers. You compare the quotes that come back and choose who to hire.
Need quotes? Describe the job once, then compare what comes back. Request quotes with one form →
What the in-place leak test does
An installed-filter leak test checks the filter media, the frame and the seal to the housing for unfiltered bypass. ISO 14644-3 includes installed filter leakage among its cleanroom test methods. IEST-RP-CC034 (current edition IEST-RP-CC034.5, July 2022) covers HEPA and ULPA leak tests at the factory, at the job site and after installation.
A typical in-place scan:
- Airflow through the filter is checked first, so the test runs at the specified velocity.
- A challenge aerosol is introduced upstream of the filter.
- The upstream concentration is measured and used as the 100% reference.
- The downstream face and perimeter are scanned with a photometer probe in overlapping strokes.
- Under common practice from IEST-RP-CC034 and ISO 14644-3, an individual leak should not exceed 0.01% of the upstream challenge.
For the service, quotes and bundling with other tests, see HEPA filter testing.
What DOP is, and why it was replaced
"DOP" is di-(2-ethylhexyl) phthalate, also called DEHP. It was used for many years as the challenge aerosol for HEPA filter testing. A 1995 U.S. Department of Energy report noted that DEHP induced liver tumors in laboratory animals and reviewed substitutes.
People still search for "DOP testing," and some SOPs still use that name. In most current in-place work the aerosol is PAO (poly-alpha-olefin). If a quote, SOP or report says "DOP test," ask which agent will actually be used.
What PAO is
PAO is now the typical challenge agent for in-place HEPA and ULPA leak tests. The test method does not change because the agent does: aerosol is still introduced upstream, and the downstream face is scanned for leaks against the same kind of acceptance criterion.
If your SOP, customer or regulator names a specific agent, or requires a particle-counter scan instead of a photometer, put that in the quote request so providers price the method you need.
What to include in your quote request
- Facility address and where the filters sit (ceiling, terminal housings, hoods, BSCs, isolators)
- Number and size of HEPA or ULPA filters, if known
- Whether housings have upstream challenge or sample ports
- The challenge agent or method your SOP requires (PAO, another named agent, photometer or particle-counter scan)
- Whether you want repair or replacement quoted if a filter fails
- Other tests for the same visit (particle counts, airflow, BSC or hood certification)
- Due date and report requirements
Need quotes? Describe the filters and the method once. Request quotes with one form →
Related services and guides
FAQ
Is DOP testing the same as PAO testing?
The leak test is the same idea: a challenge aerosol upstream of the filter and a downstream scan for leaks. DOP (DEHP) is the older agent; PAO is the typical agent used today. Confirm the agent your SOP names.
Why did PAO replace DOP?
A 1995 U.S. Department of Energy report on DEHP (DOP) noted liver tumors in laboratory animals and reviewed substitute challenge agents. PAO became the typical in-place agent after that shift.
What reading counts as a HEPA filter leak?
Under common practice from IEST-RP-CC034 and ISO 14644-3, an individual leak should not exceed 0.01% of the upstream challenge concentration.
Can room filters and cabinet filters be tested in one visit?
Yes. List every filter and cabinet in one request.
Ready to request quotes without filling out a new form for every provider? Request quotes with one form →
Are you a certification or testing company? Join as a provider →